While LonMaker uses the "xxxVNI" NI Application, some third-party network integration tools use the "NSIxxx" or "xxxL7" NI Applications. Check with the network integration tool documentation for the required NI Application type. If you select the wrong one, your network integration tool may not work with the network interface.
Change the NI application to either "NSIPCLTA" or "PCC10L7" and then press the "Apply" button. Failure to press the "Apply" button could put this applet in the wrong mode.
Test button
Press the "Diagnostics" button in the LonWorks Plug 'n Play applet. Then press the "Test" button. If you get statistics that are similar to the following, your card is working fine.
LonWorks® PCC10/PCLTA10/PCLTA20 Device Driver Version: 2.01 Card Type: PCLTA-20 / LMPA Driver Status: Loaded Image Size: 57344 Interrupt Count: 126261 ------ Network Interface Node Status ------ CRC Errors: [00000] TX Timeouts: [00000] Lost (APP) Messages: [00000] Missed (NET) Messages: [00000] Most recent error: 0 Reset Cause: External
Note that some CRC errors are expected on a LonWorks channel and do not mean there is a problem with the channel. You should only be concerned if you see a lot of CRC errors between consecutive "Test" results.
Comm button
The "Comm" button can be used to
test whether your card can send or receive a packet from/to the network,
such as a service pin message. Before using this feature, you may need
to change the NI application. Like above, change it to either "NSIPCLTA"
or "PCC10L7" and press the "Apply" button. Then press the "Diagnostics"
button.
Use the "Comm" button to test whether or not your card can receive service pin message from the network. Press the "Comm" button, and select"Yes" when you are asked "Do you want to proceed?" The Diagnostics window should display "Now waiting for a service pin message." Go ahead and press the service pin on any device on the network that is connected to the card to make the device send out a service pin message. If the card is working properly, you will receive the service pin message and you will see the following message in the Diagnostics window, indicating that your card received the message.
Received service pin, pinging node: Neuron ID: 00 03 70 97 25 00 Program ID: 80 00 01 05 33 8A 04 03 ** Ping Passed ** ** Ping Passed ** ** Ping Passed **
Press the "Quit" button to terminate the test, otherwise the "Ping Passed" message will continue to show up.
Service button
To test if your network interface
card can send out a service pin message to the network, use the
"Service" button. If you press this button, you will see the following
message:
Sending service pin message.
If you have another network interface card that can monitor the
service pin message, you can tell if your card is sending out the
packet. You can also use the LonManager Protocol Analyzer to see if the
packet has been sent out to the network.
Don't forget to change the NI Application name back to the original application and press the "Apply" button. The "Apply" button must be pressed in order to change the application type. Failure to do so may cause your Network Integration tool to fail.
- PCC-10
- PCLTA-10
- PCLTA-20
- PCLTA-21