The IP-852 Configuration Server should always be running 
before opening any existing LonMaker/LNS network when using IP-852 for 
the network Interface (NSD). 
That is, the IP-852 Configuration 
Server needs to be running before you open any IP-852 LonMaker/LNS 
database in addition to making changes to the LNS database like 
adding/deleting devices/FBs/connections.  Failure to do so may affect 
LonMaker/LNS Monitor and Control of the network.
Problem:
If you have created an IP-852 Channel and associated members with the
 IP-852 Configuration Server running and you close the LonMaker/LNS 
database before closing the IP-852 Configuration Server, the 
Configuration server will tell the PC IP-852 NSD and all the i.LONs that
 the PC network interface is no longer running.  If you then open the 
LonMaker/LNS database without the IP-852 Configuration Server running 
the LonMaker/LNS App can communicate to the i.LONs but the LNS/OpenLNS 
Server may not see the i.LON response.  
In this case, 
LonMaker/LNS monitor and control may not work properly.  Once you open 
the IP-852 Config Server and the Config Server has communicated to the 
i.LONs, Monitor and Control will start working again.
There is no problem if you close the IP-852 Config Server before closing the LonMaker/LNS database.
Recommendations:
- Make sure the IP-852 Configuration Server is running before opening a LonMaker/LNS database using IP-852.
 - If you are running LNS or OpenLNS Server as a service and you have at least one network using IP-852, you should have the IP-852 added to your PC startup menu.